Type A/H-ERC Panel, Large (33" Wide x 45" High) | |||||||||||||||
![]() | |||||||||||||||
A/HM-HRC SMALL PANEL PIPING DIAGRAM | |||||||||||||||
![]() | |||||||||||||||
|
Mount the panel on a rigid vertical support, low enough for the 1/2" air line from the compressor to slope down to the air reservoir. This permits moisture to drain to the reservoir where it can be automatically ejected by the moisture valve. Pipe and wire the panel into the system per applicable connection diagrams. After the brake system is completely piped and wired, turn power ON. Check preset air pressures: | |
|
|
SPECIAL BLEEDING AND PRESSURE ADJUSTMENT INSTRUCTIONS FOR A/H-ERC SYSTEM | |
|
should control the loaded crane to a quick stop without abnormal load swing. Either pressure steps may be reset in field; however, low pressure step must be less than the high pressure step. Note: Power failure or power shutdown causes high pressure step to apply but initiates slow air pressure bleed-down, which causes complete brake release after 1-2 hours. |
TYPE A/HM-ERC AIR/HYDRAULIC PREWIRED CONTROL PANEL |
TYPE A/H-ERC AIR/HYDRAULIC PREWIRED CONTROL PANEL |
![]() |
![]() |
| Note: Standard AC Panels Are Designed For 460V operation. |
1PS - N.C. compressor Start-Stop Pressure Switch (80/65 PSI) 2PS - N.O. System Pressure Switch (60/50 PSI) BPB - Bleeder Pushbutton BFP - Service Brake Filling Pushbutton |